Products


+
  • 02(1712124284776).png
  • 01(1712124284602).png

Double-fed-1140V
3.x-6.xMW


Product Classification:

Doubly-Fed Wind Converter

Key Words: Converter

Online Message

Product Introduction

power 3.0MW/3.3MW/3.6MW 4.0MW/4.2MW/4.5MW/4.8MW 5.2MW/5.5MW 6.0MW/6.25MW/6.66MW/6.76MW
model HD06DF3000
HD06DF3300
HD06DF3600
HD06DF4000
HD06DF4200
HD06DF4500
HD06DF4800
HD06DF5200
HD06DF5500
HD06DF6000
HD06DF6250
HD06DF6660
HD06DF6760
Dimensions (W*H*D) 2600*2200*600mm 2600*2200*600mm 2600*2200*800mm 2600*2200*800mm
Operating altitude 0~3000m 0~3000m 0~3000m 0~3000m
noise <82dB <82dB <82dB <82dB
Working temperature -30℃~+45℃, current derating above 45℃, current derating 2% for every 1℃ increase in temperature, shutdown at 50℃
cooling method Air Cooling Air Cooling Air Cooling Air Cooling
Protection level Grid cabinet IP23
Control cabinet IP54
Power cabinet IP23
Grid cabinet IP23
Control cabinet IP54
Power cabinet IP23
Grid cabinet IP23
Control cabinet IP54
Power cabinet IP23
Grid cabinet IP23
Control cabinet IP54
Power cabinet IP23
Grid parameters
power voltage 1140V+15%/-10% 1140V 1140V+15%/-10% 1140V±10%
Frequency Range 47Hz~53Hz 47.5Hz~52.5Hz 47.5Hz~55Hz 46.5Hz~51.5Hz
Grid-side converter parameters
Rated current 277A/300A/350A 397A/415A/446A/474A 516A/546A 595A/621A/637A/646A
Machine measurement of converter parameters
Rated current 656A 760A/800A/880A/910A 1017A/1076A 1010A/1110A/1200A/1200A

 

 

The control circuit of the converter separates the loop control circuit and the closed loop control circuit according to the control mode. The former is mainly used in some special equipment with low requirements; the latter has the function of automatic control and adjustment, and is widely used in various working machines.
According to the nature of the control signal, it is divided into analog control circuit and digital control circuit. Analog signal is the most commonly used DC voltage and current, easy to use the method of electricity to be processed and transformed; digital signal is a set of information parameters with discrete values of the discontinuous change of the signal. Digital control has high precision, but the circuit is more complex and expensive. Therefore, digital-analog hybrid control circuits are widely used in practice. In addition, the control circuit using the microcomputer also has many advantages.

Related Products

215/233kWh<br />C&I Energy Storage System

<ul> <li>High efficient single cluster management</li> <li>High efficient heat management technology extending system lifespan</li> <li>High quality cell in high consistency with cell health big data management</li> <li>Multi-stage protection, suitable for multi-scenario applications</li> <li>Modular design, high energy density, small footprint, easy for operation and maintainance</li> <li>Intelligent monitoring, fast fault positioning</li> <li>Multiple operation mode optional</li> <li>Flexible parallel connection and easy system expansion, eliminating DC circulating current and reducing parallel capacity loss</li> </ul>

630kW Centralized PCS

<ul> <li>Wide DC bus voltage range</li> <li>Intelligent multi-grade fan speed regulation, no derating from -30℃to +50℃</li> <li>All around the clock ground insulation monitoring, ensuring the safety of thesystem</li> <li>Intelligent wave recording and local touch screen monitoring, fast incident and fault positioning</li> <li>Flexible parallel connection and easy system expansion</li> <li>Compatible with various batteries</li> <li>Smooth switch between Grid and Off-grid mode, "black start" function integrated</li> <li>Equipped with functions like VSG, PQ , VF, etc., support L/HVRT, FRT</li> </ul>

2750/3150/3450kW Converter Booster Integrated Machine

<ul> <li>Wide DC bus voltage range</li> <li>All around the clock ground insulation monitoring, ensuring the safety of the system</li> <li>Intelligent wave recording and local touch screen monitoring, fast incident and fault positioning</li> <li>Flexible configuration of voltage class, circuit breaker, etc.</li> <li>Grid forming function, alleviate transient voltage and frequency instability in the power system</li> <li>IP 55 protection on the entire body, suitable for various harsh environments</li> <li>Support IEC 61850 protocol, rapid power response</li> </ul>

Immediate Consultation

If you are interested in our products, please leave your email, we will contact you as soon as possible, thank you!

Submit Message